MAXDATA SN 40 M1 Betriebsanleitung Seite 54

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 80
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 53
Commissioning
54
Tank linearization
Example:
G09-RIA452ZZ-15-00-xx-xx-011
Fig. 22: Example for tank linearization
You want to determine the amount of cereal filled into a silo, display this information on site and
transfer it to a process control system. A 4-20 mA level sensor determines the level in the
container, the connection between the level (m) and volume (m
3
) is known and the level is
proportional to the sensor current. The volume calculated is output as a 0-20 mA signal at the
analog output in proportion to the volume. In the event of a fault in the system, the analog
output outputs an error signal of 21.0 mA.
Container empty:
Sensor signal 4 mA
Level 0 m
Numeric display should show 0 (m
3
)
Bar graph should show 0%
0 mA should be present at the analog output
Container full:
Sensor signal 20 mA
Show points
No
Yes
Show all programmed support cells.
Function
(menu
item)
Parameter setting Description
Seitenansicht 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 79 80

Kommentare zu diesen Handbüchern

Keine Kommentare